SI-200IS

Built-in Sensor Monitoring Panel

The SI-200IS is an integrated model that combines a gas sensor with a receiver unit, featuring a large F.N.D (Fluorescent Numeric Display) for displaying gas concentration levels.

KEY FEATURES
    • Integrated Sensor Type: Supports O₂, toxic, or combustible gases (%LEL)
    • Self-diagnostic Test Function: Automatically checks device status
    • 4-digit BIG F.N.D Display: Large numerical display for better visibility
    • 4-20mA / RS-485 Signal Output: Compatible with various monitoring systems
    • 3-step Alarm LED & Relay Output: Visual alarm indicators and relay contact output by alarm level
    • Configurable Alarm Setpoints and Delay Time: Customizable user settings
    • Built-in Li-ion Battery: Displays available usage time in minutes
    • Wall Mount Type: Easy and secure installation
    • Peak Hold: Displays the highest detected value
Product Inquiry

SI-200IS

Built-in Sensor Monitoring Panel

DESCRIPTION

The SI-200IS is an integrated model combining a gas sensor with a receiver unit, featuring a large F.N.D (Fluorescent Numeric Display) for clear gas concentration readings.


KEY FEATURES

- Integrated Sensor Type: Supports O₂, toxic, or combustible gases (%LEL)
- Self-diagnostic Test Function: Automatically checks device status
- 4-digit BIG F.N.D Display: Large numerical display for better visibility
- 4-20mA / RS-485 Signal Output: Compatible with various monitoring systems
- 3-step Alarm LED & Relay Output: Visual alarms and relay contacts by level
- Configurable Alarm Setpoints and Delay Time: User-customizable settings
- Built-in Li-ion Battery: Displays available usage time in minutes
- Wall Mount Type: Easy and secure installation
- Peak Hold: Displays the highest detected value


Product Specifications
ModelSI-200IS (Built-in SENSOR MONITORING PANEL)
Measuring OutputBig FND display (4-digit), 9-LED
EnclosureNon-explosion Proof type
Detectible GasO₂, Toxic, Combustible Gas
Measuring Display4-Digit Big FND Digital Display
Measuring MethodDiffusion Type
AccuracyFND Digital ±1% Full Scale or 1 Digit (Whichever is greater)
Input Signal4-20mA Full Scale
Operation Temperature-20 to 50°C
Operation Humidity5% to 99% RH (Non-condensing)
Output Signal 24V.DC / 4-20mA DC / RS-485 Modbus
Dry Contact Output: 3mA / Correction Output: 3mA / Fault Output: 0mA
Alarm Display LED Display: 3-Alarm, Trouble, BATT, B/Z STOP, RESET, Warning
Audible: Buzzer (85dB)
Relay ContactAC 250V / 3A (Alarm1, Alarm2, Alarm3, Fault)
Power SupplyInput: 100~250V.AC
Back-Up BatteryLi-ion Rechargeable Battery, 7.3V, 2,850mAh
Battery DisplayBattery Error LED, Operating time FND Display
Battery Operating Time1 to 2 hours or more
CableStandard type: (CVVS or CVVSB 1.5sq t)+Shield
Cable Connection Length 4-20mA DC Signal: 2,500m
RS-485 Modbus Signal: 1,000m
Mounting TypeWall mounting type
IP CodeIP65
Dimensions & Weight231(W) x 397.5(H) x 117(D) mm / 2kg